Resolution No. 572RESOLUTION NO. 572
A RESOLUTION AUTHORIZING THE PRESIDENT OF THE
BOARD OF DIRECTORS OF SOUTH TAHOE PUBLIC UTILITY
DISTRICT TO EXECUTE TWO SERVICE AGREEMENTS WITH
SIERRA PACIFIC POWER COMPANY.
BE IT RESOLVED by the Board of Directors of the SOUTH
TAHOE PUBLIC ~TILITY DISTRICT, County of E1 Dorado, State of
California, as follows:
1. That the President of the Board of Directors of
SOUTH TAHOE PUBLIC UTILITY DISTRICT be, and he is hereby
authorized to execute two (2) Service Agreements for Rate
Schedule A-2 which offers electric energy for SOUTH TAHOE
PUBLIC UTILITY DISTRICT at, One (1) Bijou Pumping Station,
and Two (2) Pumps at Holding Pond, which said Service
Agreement is attached to this Resolution and incorporated
herein by reference.
PASSED AND ADOPTED at a regular meeting of the Board of
Directors of South Tahoe Public Utility District on July 1, 1965
by the following vote:
AYES: Directors Clarke, Wakeman, Fesler, Stewart and
Kortes
NOES: None
ABSENT: None
Db~ald L. ~'larke, President "-
of the Board of Directors of
South Tahoe Public Utility
District
David W. Callahan, Clerk of the
South Tahoe Public Utility District
and ex officio Secretary of the
Board of Directors thereof
(SEAL)
) os.
~uaty ef BI Dorado)
it a ~y ~Id ~Suhr Me~luS on July t, ~, ~ t~ C~
by t~ ~l~t~ ~tm ol ~ ~rl of t~ ~g of M~r8
thereo~ ~
Korte$
and ex Offte~o bereUr7
(SUL)
~ PACNqC IK~WER CO.
BINO, NEVADA
Revised Cal. P.U.C. Sheet No. 257oE
Canceling Revised C.R.C. Sheet No. 24-E
Schedule No. A-2
GENERAL SERVICE
APPLICABILITY
This schedule is applicable to all single and three-phase alternating
current service including power and lighting provided that all single-phase
or three-phase service hereunder be taken at one point of delivery.
TERRITORY
Entire service territory.
RATES
Per Meter
Demand Charge: Per Month
First
Ail Excess
50 kw or less of billing demand ......... $ 115.00
kw of billing demand, per kw ......... 2.30
Energy Charge (to be added to demand charge):
First
Next
Next
Next
All Excess
3000 kwhr, per kwhr .................... 1.70¢
3000 kwhr, per kwhr .................... 1.50¢
3000 kwhr, per kwhr .................... 1.30¢
3000 kwhr, per kwhr .................... 1.05¢
kwhr, per kwhr .................... 0.80¢
Minimum Charge:
The monthly minimum charge shall be the monthly demand charge.
SPECIAL CONDITIONS
Voltage: Service on this schedule will be supplied at one standard
voltage. Service may be supplied under this schedule at 120/208
volts four-wire wye or at 277/480 volts four-wire wye, provided:
(1) written application is made for such service by the Customer;
(2) the Customer's loud is of such size as to require an individual
transformer installation of not less than 150 kva of transformer
capacity for 120/208 volt service or not less than 300 kva of
transformer capacity for 277/480 volt service; and (3) the Customer
provides space acceptable to the Utility on his premises to ac-
commodate the installation of the Utility's facilt~i&s. The fore-
going conditions do not apply where the Utility maintains four-
wire wye connected polyphase mains.
(Continued)
Advice Lett~ No ............... A.& .......
D~cisic~ ~ ................6~6 .......
............... E~:~4..L....~F.k~ ~ke.K ............
President
~ro bo Jflmrted by Gal. P.U.C.!
....... ..............
........ ..... ...............
Resolution No ...........................
........... .R.e...v.L~.e..d. ............ Cal. P.U.C. Sheet No ............................. .2..5..8..T-E-
Canceling ........... ..Rq....v..~.~.d. ............ Cal. P.U.C. Sheet No ............................ .]:9_.0.'..E.
Schedule No. A-2
GENERAL SERVICE
SPECIAL CONDITIONS (Continued)
Billing Demand: The billing demand hereunder for any billing
period shall be the greater of the current period's measured
demand; or fifty percent (50%) of the highest billing demand
established by the Customer during the preceding eleven months;
or fifty kilowatts (50 kw).
Be
Maximum Demand Measurement: The demand for any billing shall be
defined as the maximum measured fifteen minute average kilowatt
load in the billing period. In instances, however, where the use
of energy by a Customer is intermittent and subject to violent
fluctuations, a shorter time interval may be used and the demand
determined from special measurements.
At the Utility's option, a thermal type of demand meter which
does not reset after a definite time. interval may be used for
demand measurements.
e
Primary Metering: Whenever for the convenience of the Utility
service is metered hereunder at the available primary distribution
voltage, the demand charge and energy charge of the rate above
shall be reduced by two and one-half percent (2-1/270.
e
Power Factor: The Utility may, at its option, measure the average
power factor of any Customer load served hereunder. Whenever the
billing demand of such Customer in any month exceeds four hundred
kilowatts (400 kw), the demand charge and energy charge of the
rate above shall be decreased or increased, respectively, fifteen-
hundredths of one percent (0.15%) for each one percent (1%) that
the average power factor of such Customer's load during such month
is more than or less than eighty percent <80~.) lagging. The aver-
age power factor shall be computed (to the nearest whole percent)
from the ratio of total lagging reactive kilovolt-ampere-hours
to total kilOWatt-hours.
6. Contracts: A contract will be required foz service hereunder
for a minimum term of not less than one year.
Ite be Immed IW mfllttl
Advice Letter No ............ .z$.8.. ..........
Decision No ..............6..7..6..8..6 ..........
luued by
Fred L. Fletcher
President
ITo I~ ~ I~ Cal. ~'.U.C.I
Date Filed ........$.[...P...~...~. _ ! .g..8..4. .............
E, ........ ..... ...............
Resolution No ...................................