TK761-TK760South Tahoe Public Utility District
Inspection report
Date :Work Order :Pipe Segment Ref. :Weather :Surveyed By :Certificate Number :
Year laid :Pre-cleaning :Pipe Joint Length :Direction :Total Length :Length Surveyed :
WinCanVX Master Server // Page: 1
City :SLT Drainage Area :K-29 Upstream MH :TK761
Street :Shop St Media Label :Up Rim to Invert :0.0
Location Code :Flow Control :Downstream MH :TK760
Location Details :Sheet Number :Down Rim to Invert :0.0
Pipe shape:Circular Sewer Use:
Pipe size:6 Sewer Category :SEC
Pipe material:Vitrified Clay Pipe Purpose:
Lining Method :Owner :
Additional Info :
1:2246 Distance Code Observation Counter Photo Grade
0.00 AMH Manhole / TK761 00:00:00
0.00 MWL Water Level, 5% of cross sectional area 00:00:00
14.20 JSM Joint Separated Medium / Dirt at Joints S1
79.50 VZ Vermin Other, quantity:, 1 M1
182.50 TFD Tap Factory Made Defective at 9 o'clock, 4inch dim /
Roots
M2
182.50 RMC Roots Medium Connection from 8 o'clock to 10 o'clock,
15% lost
M3
184.10 RFJ Roots Fine Joint from 12 o'clock to 12 o'clock, within 8
inch
M1
184.60 TFD Tap Factory Made Defective at 3 o'clock, 4inch dim /
Roots
M2
291.30 MWM Water Mark, 50% of cross sectional area M4
297.50 AMH Manhole / TK760
6/5/2018 JASON CHATHAM U-1207-6103 TK761-TK760
Jetting Downstream 297.5 297.5
QSR QMR SPR MPR OPR SPRI MPRI OPRI
1100 4131 1.0 13.0 1.0 2.2 2.014.0
TK761
South Tahoe Public Utility District
Page 2
Section Pictures - 6/5/2018 - TK761-TK760
SLT Shop St 6/5/2018 TK761-TK760 218
, 00:00:00, 0.00
Water Level, 5% of cross sectional area
, , 79.50
Vermin Other, quantity:, 1
, , 14.20
Joint Separated Medium / Dirt at Joints
, , 182.50
Tap Factory Made Defective at 9 o'clock, 4inch dim / Roots
City Street Date Pipe Segment Reference Nr.
South Tahoe Public Utility District
Page 3
Section Pictures - 6/5/2018 - TK761-TK760
SLT Shop St 6/5/2018 TK761-TK760 218
, , 182.50
Roots Medium Connection from 8 o'clock to 10 o'clock, 15%
lost
, , 184.60
Tap Factory Made Defective at 3 o'clock, 4inch dim / Roots
, , 184.10
Roots Fine Joint from 12 o'clock to 12 o'clock, within 8 inch
, , 291.30
Water Mark, 50% of cross sectional area
City Street Date Pipe Segment Reference Nr.
South Tahoe Public Utility District
Page 4
ScanExplorer Overview - 6/5/2018 - TK761-TK760
SLT Shop St 6/5/2018 TK761-TK760 _24
City Street Date Pipe Segment Reference
South Tahoe Public Utility District
Page 5
ScanExplorer Overview - 6/5/2018 - TK761-TK760
SLT Shop St 6/5/2018 TK761-TK760 _24
City Street Date Pipe Segment Reference
Legend
Distance PACP Code Observation
(1)0.00 AMH Manhole
(2)0.00 MWL Water Level, 5% of cross sectional area
(3)14.20 JSM Joint Separated Medium
(4)79.50 VZ Vermin Other, quantity:, 1
(5)182.50 TFD Tap Factory Made Defective at 9 o'clock, 4inch dim
(6)182.50 RMC Roots Medium Connection from 8 o'clock to 10 o'clock, 15% lost
(7)184.10 RFJ Roots Fine Joint from 12 o'clock to 12 o'clock, within 8 inch
(8)184.60 TFD Tap Factory Made Defective at 3 o'clock, 4inch dim
(9)291.30 MWM Water Mark, 50% of cross sectional area
(10)297.50 AMH Manhole